Urządzenie CGIW Eco 100..400 kW

CGIW Eco 100...400 kW

Model CGIW n-n-V-P1-P2-P3-Eco, details of type and technical values available from the selection program

 

32-4

36-4

42-4

44-4

48-4

Cooling output kW 113 131 142 148 171
Free-cooling output kW*

87

101

109

116

130

Free-cooling output kW**

66

75

82

87

97

           
Power type V-Ph-Hz

400-3-50

400-3-50

400-3-50

400-3-50

400-3-50

Connected loadkW 45,7 51,7 55,7 58,8 66,8
Operating current A 91,2 103,2 111,2 117,8 133,8
Pre-cutout A (slow) 100 125 160 160 160
           
Circuits 2 2 2 2 2
           
Refrigerant kg R410A 12,6 15,2 16,2 18,0 18,0

Header tank l

800

800

800

800

800

           
Dimensions          
Length mm 3450 3450 3450 3450 3450
Width mm 900 900 900 900 900
Height mm 1950 1950 1950 1950 1950
Freightage weight kg 1620 1680 1740 1755 1830
Operating weight kg 2470 2550 2620 2640 2720
         

 

 

56-4

64-4

72-4

80-4

90-4

100-4

Cooling output kW 196 232

250

285 315 350
Free-cooling output kW*

155

183

197

224

248

276

Free-cooling output kW**

110

138

148

169

187

207

             
Power type V-Ph-Hz

400-3-50

400-3-50

400-3-50

400-3-50

400-3-50

400-3-50

Connected load kW 76,8 87,2 99,0 110,0

121,5

133,5

Operating current A 153,4 174,6 193,9 211,9

235,3

258,5

Pre-cutout A (slow) 200 200 250 250

315

315

             
Circuits 2 2 2 2 2 2
             
Refrigerant kg R410A 24,0 30,0 32,0 34,0

34,0

36,0

Header tank, l

800

800

800

800

800

800

             
Dimensions            
             
Length mm 3950 3950 3950 3950 3950 3950
Width mm 900 900 900 900 900 900
Height mm 1950 1950 1950 1950 1950 1950
Freightage weight kg 1950 2200 2260 2290

2370

2430

Operating weight kg 2850 3010 3075 3120

3205

3275

 

Cooling output is given with the following values:

  • Evaporator 7/12 °C, condenser 36/42 °C
  • Ethylene glycol content 35 %
  • Free-cooling output: outdoor temperature *(+2°C) ja **(+4°C) water 9 / 14 °C
  • Connected load: compressors and pump (with liquid chiller fans to be stated separately)
  • Operating current: suction pressure 5 bar, condensation pressure 21 bar

Extrapolation from the output table is not permitted. Final technical selection to be made from our dimensioning software. Chiller Oy reserves the right to make changes without separate notice.