CGIW 45?100 kW

Model CGIW n-n-V-P1-P2-(P3), details of type and technical values available from the selection program

           
 

12-2

16-2

20-2

24-2

 

Cooling output kW 41 57 74 85  
           
Power type V-Ph-Hz

400-3-50

400-3-50

400-3-50

400-3-50

 

Connected load kW 17,8 22,7 28,9 33,1  
Operating current A 36,0 46,0 58,4 66,5  
Pre-cutout A (slow) 50 63 80 80  
           
Circuits 2 2 2 2  
           
Refrigerant kg R410A 7,2 7,2 8,0 9,0  
Header tank l 300 300 300 300  
           
Dimensions          
Length mm 1790 1790 1790 1790  
Width mm 750 750 750 750  
Height mm 1850 1850 1850 1850  
Freightage weight kg 620 650 665 685  
Operating weight kg 1055 1100 1110 1165  

Cooling output is given with the following values

  • Evaporator 7/12 °C, condenser 36/42 °C
  • Ethylene glycol content 35 %
  • in CGIA units, the cooling output is given at a condensation temperature of 45 °C
  • Connected load: compressors (additional equipment pumps,
    liquid chiller or condenser - fans stated separately)
  • Operating current: suction pressure 5 bar, condensation pressure 21 bar
     
    (P3) only in model CGIW. Extrapolation from the output table is not permitted.
    Final technical selections to be made from our dimensioning software.
    Chiller Oy reserves the right to make changes without separate notice.

Brochure CHSAM100064ENA.pdf