Device size 50?60 kW dual-circuit

 

Technical data with refrigerant R-407C (DX-radiator)
     
AUC = upward blowing direct condensation
ADC = downward blowing direct condensation
     
Nominal chilling output at room temperature 24? C, 50 %, condensation temperature 45? C
Dual-circuit units    
Device type 130-2 140-2
Total output kW 50 58
Sensible output kW 46 49
Chilling output requirement kW 65 75
     
Compressors (hermetic) 400V-3ph-50Hz
Number 2 2
Power requirement kW 15 18
     
Centrifugal fans 230V-1Ph-50Hz direct drive
Number 3 3
Air quantity m3/s 3,18 3,18
External pressure Pa 60 60
Motor output kW 2,25 2,25
     
Filters EU5    
Number 3 3
Size: upward blowing 600x600 600x600
Size: downward blowing 560x650 560x650
     
After-heating 400V-3Ph-50Hz  
Heating output kW 12 12
Number of elements 4 4
Number of steps 3 3
     
Humidification 400V-3Ph-50Hz  
Humidification output kg 9,4 9,4
Connected load kW 6,9 6,9
     
Dimensions and weight    
Width mm 2300 2300
Depth mm 650 650
Height mm 1920 1920
Weight kg 490 490
Exhaust chamber height 500 mm
(to be added to height of unit, models AUC, WUC)
     
Connections    
Humidifier mm 6 6
Drain mm 32 32
     
Unit´s electrical connected load 400V-3Ph-50Hz
Types A and E kW 17,5 21,0
Type B kW 29,3 33,0
Type C kW 24,2 27,9
Type D kW 36,2 39,9
     
     
Condenser selections  
AUC and ADC units    
     
Device type 130-2 140-2
Condensing output requirement kW 65 75
     
Condensers (outdoor temperature 30°C, condensation temperature 45°C)
     
Alternative 1 CCS 13-9 CCS 14-9
Noise level dB(A) at 10-m distance 48 49
     
Alternative 2 CCS 11-14 CCS 12-14
Noise level dB(A) at 10-m distance 60 58