Technical data with refrigerant R-407C (DX-radiator) | ||
AUC = upward blowing direct condensation | ||
ADC = downward blowing direct condensation | ||
Nominal chilling output at room temperature 24? C, 50 %, condensation temperature 45? C | ||
Dual-circuit units | ||
Device type | 130-2 | 140-2 |
Total output kW | 50 | 58 |
Sensible output kW | 46 | 49 |
Chilling output requirement kW | 65 | 75 |
Compressors (hermetic) 400V-3ph-50Hz | ||
Number | 2 | 2 |
Power requirement kW | 15 | 18 |
Centrifugal fans 230V-1Ph-50Hz direct drive | ||
Number | 3 | 3 |
Air quantity m3/s | 3,18 | 3,18 |
External pressure Pa | 60 | 60 |
Motor output kW | 2,25 | 2,25 |
Filters EU5 | ||
Number | 3 | 3 |
Size: upward blowing | 600x600 | 600x600 |
Size: downward blowing | 560x650 | 560x650 |
After-heating 400V-3Ph-50Hz | ||
Heating output kW | 12 | 12 |
Number of elements | 4 | 4 |
Number of steps | 3 | 3 |
Humidification 400V-3Ph-50Hz | ||
Humidification output kg | 9,4 | 9,4 |
Connected load kW | 6,9 | 6,9 |
Dimensions and weight | ||
Width mm | 2300 | 2300 |
Depth mm | 650 | 650 |
Height mm | 1920 | 1920 |
Weight kg | 490 | 490 |
Exhaust chamber height 500 mm | ||
(to be added to height of unit, models AUC, WUC) | ||
Connections | ||
Humidifier mm | 6 | 6 |
Drain mm | 32 | 32 |
Unit´s electrical connected load 400V-3Ph-50Hz | ||
Types A and E kW | 17,5 | 21,0 |
Type B kW | 29,3 | 33,0 |
Type C kW | 24,2 | 27,9 |
Type D kW | 36,2 | 39,9 |
Condenser selections | ||
AUC and ADC units | ||
Device type | 130-2 | 140-2 |
Condensing output requirement kW | 65 | 75 |
Condensers (outdoor temperature 30°C, condensation temperature 45°C) | ||
Alternative 1 | CCS 13-9 | CCS 14-9 |
Noise level dB(A) at 10-m distance | 48 | 49 |
Alternative 2 | CCS 11-14 | CCS 12-14 |
Noise level dB(A) at 10-m distance | 60 | 58 |