Model CGIA n-n-V-P1-P2-(P3), details of type and technical values available from the selection program |
|||||
12-2 |
16-2 |
20-2 |
24-2 |
|
|
Cooling output kW | 41 | 57 | 74 | 85 | |
Power type V-Ph-Hz |
400-3-50 |
400-3-50 |
400-3-50 |
400-3-50 |
|
Connected load kW | 17,8 | 22,7 | 28,9 | 33,1 | |
Operating current A | 36,0 | 46,0 | 58,4 | 66,5 | |
Pre-cutout A (slow) | 50 | 63 | 80 | 80 | |
Circuits | 2 | 2 | 2 | 2 | |
Refrigerant kg R410A | 7,2 | 7,2 | 8,0 | 9,0 | |
Header tank l |
300 |
300 |
300 |
300 |
|
Dimensions | |||||
Length mm | 1790 | 1790 | 1790 | 1790 | |
Width mm | 750 | 750 | 750 | 750 | |
Height mm | 1850 | 1850 | 1850 | 1850 | |
Freightage weight kg | 620 | 650 | 665 | 685 | |
Operating weight kg | 1055 | 1100 | 1110 | 1165 |
The cooling output is given with the following values
- Evaporator 7/12 °C, condenser 36/42 °C
- Ethylene glycol content 35 %
- in CGIA units, the cooling output is given at a condensation temperature of 45°C
- Connected load: compressors (additional equipment pumps,
liquid chiller or condenser - fans stated separately) - Operating current: suction pressure 5 bar, condensation pressure 21 bar
(P3) only in model CGIW. Extrapolation from the output table is not permitted.
Final technical selections to be made from our dimensioning software.
Chiller Oy reserves the right to make changes without separate notice.