Model CHT-12...28-2D-X-P1-P3-STD, type and selections are available from Chiller Oy´s sales engineers or from an authorized sales organization.
Model CHT | 12-2 | 16-2 | 20-2 | 24-2 | 28-2 |
Heating cap. kW | 38,5 | 50,4 | 66,6 | 74,2 | 98,9 |
Cap. adjusting | 0;50;100% | 0;50;100% | 0;50;100% | 0;50;100% | 0;50;100% |
Mains | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 |
Power input kW | 19,8 | 25,8 | 33,5 | 37,5 | 52,0 |
Running amps A | 35,1 | 43,1 | 57,2 | 67,2 | 88,4 |
Precut-out fuse A (slow) | 50 | 63 | 80 | 80 | 100 |
Nominal flows: | |||||
Cold side kg/s | 1,99 | 2,57 | 3,42 | 3,73 | 4,88 |
Hot side kg/s | 1,76 | 2,31 | 3,05 | 3,39 | 4,52 |
Refr. R410A kg | 7,2 | 7,2 | 8 | 9 | 11 |
Dimensions: | |||||
Length mm | 1790 | 1790 | 1790 | 1790 | 1790 |
Width mm | 750 | 750 | 750 | 750 | 750 |
Height mm | 1850 | 1850 | 1850 | 1850 | 1850 |
Capacity by values 0/-3°C (30% etanol) and 44/50°C (water)
Power input: compressor and pumps P1 and P3
Exact selection data from sales engineer (on base of concrete project requirements)
Chiller Oy reserves right to make changes without prior notice!