Device size 50?60 kW dual-circuit

Technical data with refrigerant R-407C (DX-radiator)
     
WUC = upward blowing with liquid chilling
WDC = downward blowing with liquid chilling
     
Nominal condensing output at room temperature 24? C, 50 %, condensation temperature 45? C
Dual-circuit units    
Device type 130-2 140-2
Total output kW 50 58
Sensible output kW 46 49
Condensing output requirement kW 65 75
     
Compressors (hermetic) 400V-3ph-50Hz
Number 2 2
Power requirement kW 15 18
     
Centrifugal fans 230V-1Ph-50Hz direct-drive
Number 3 3
Air quantity m3/s 3,18 3,18
External pressure Pa 60 60
Motor output kW 2,25 2,25
     
Filters EU5    
Number 3 3
Size: upward blowing 600x600 600x600
Size: downward blowing 560x650 560x650
     
After-heating 400V-3Ph-50Hz  
Heating output kW 12 12
Number of elements 4 4
Number of steps 3 3
     
Humidification 400V-3Ph-50Hz  
Humidification output kg 9,4 9,4
Connected load kW 6,9 6,9
     
Dimensions and weight    
Width mm 2300 2300
Depth mm 650 650
Height mm 1920 1920
Weight kg 490 490
Exhaust chamber height 500 mm  
(to be added to height of unit, model WUC)  
     
Connections    
Humidifier mm 6 6
Drain mm 32 32
     
Unit´s electrical connected load 400V-3Ph-50Hz
Types A and E kW 17,5 21,0
Type B kW 29,3 33,0
Type C kW 24,2 27,9
Type D kW 36,2 39,9
     
     
Liquid chiller selections  
WUC- and WDC units  
     
Device type 130-2 140-2
Condensing output requirement kW 65 75
     
Liquid chillers (outdoor temperature 30°C, liquid temperature 37 / 42°C (nominal value), 35 % propylene glycol)
     
Alternative 1 CCSG 15-9-50-22 CCSG 16-11-65-25
Noise level dB(A) at 10-m distance 49 51
Liquid flow l/s 3,0 3,4
Pressure drop kPa 32,5 30,9
     
Alternative 2 CCSG 14-11-65-23 CCSG 14-14-65-26
Noise level dB(A) at 10-m distance 54 51
Liquid flow l/s 3,1 3,5
Pressure drop kPa 34,1 27,6

Siirry sivun alkuun

Dimensional drawing