Dry coolers suitable for CCSG water-chiller and standard air-conditioning units
Characteristics
CCSG dry coolers are ready-to-install devices suitable for outdoor use, which include a heat-exchanger component made from copper pipe and aluminium panels, and axial fans. The same device is suitable for installation to blow both vertically (H model) and horizontally (V model).
Construction
The frame structure is made of effectively rustproofed hot-galvanized steel. Other alternatives are available to special order. The plinth structure can be adjusted between 400-760 mm at the installation point, which also allows installation on sloping surfaces.
Panel element
The spacing of the panels is 2.5 mm. Devices operating in more demanding ambient conditions are available with epoxy-coated aluminium panels.
Fans
There are four alternative rpms for the fans. The fan diameters are 350, 450, 500, and 560 mm. All 3-pH fans have double-rpm axial fan motors
D/Y 1400/1150 or 900/700 rpm.
Device selection
Computer software for selecting and dimensioning liquid-chillers is available from your supplier.
Model
|
|
|
7 |
|
|
9 |
|
|
11 |
|
|
14 |
|
CCSG |
Fans |
Cap. |
Airflow |
S.L. |
Cap. |
Airflow |
S.L. |
Cap. |
Airflow |
S.L. |
Cap. |
Airflow |
S.L. |
|
No. |
kW |
m3/s |
dB(A) |
kW |
m3/s |
dB(A) |
kW |
m3/s |
dB(A) |
kW |
m3/s |
dB(A) |
1 |
1 x 350 |
- |
- |
- |
- |
- |
- |
- |
0,45 |
36 |
- |
0,60 |
42 |
2 |
1 x 350 |
- |
- |
- |
- |
- |
- |
- |
0,60 |
36 |
- |
0,70 |
42 |
3 |
1 x 450 |
- |
0,60 |
33 |
- |
0,82 |
41 |
- |
1,05 |
45 |
- |
1,30 |
51 |
4 |
1 x 450 |
- |
0,70 |
33 |
- |
0,92 |
41 |
- |
1,16 |
45 |
- |
1,50 |
51 |
5 |
1 x 500 |
- |
0,79 |
33 |
- |
1,12 |
42 |
- |
1,30 |
45 |
- |
1,90 |
52 |
6 |
1 x 560 |
- |
1,19 |
34 |
- |
1,74 |
42 |
- |
2,12 |
48 |
- |
2,56 |
55 |
7 |
2 x 450 |
- |
1,47 |
36 |
- |
1,81 |
44 |
- |
2,30 |
48 |
- |
3,00 |
54 |
8 |
2 x 500 |
- |
1,58 |
36 |
- |
2,25 |
45 |
- |
2,63 |
48 |
- |
3,97 |
55 |
9 |
2 x 560 |
- |
2,15 |
37 |
- |
3,00 |
45 |
- |
3,50 |
51 |
- |
4,50 |
58 |
10 |
3 x 500 |
- |
2,40 |
38 |
- |
3,36 |
46 |
- |
3,90 |
49 |
- |
5,70 |
56 |
11 |
3 x 560 |
- |
3,10 |
39 |
- |
4,50 |
46 |
- |
5,30 |
52 |
- |
6,60 |
60 |
12 |
4 x 500 |
- |
3,10 |
40 |
- |
4,58 |
48 |
- |
5,30 |
50 |
- |
7,20 |
58 |
13 |
4 x 560 |
- |
4,00 |
40 |
- |
5,60 |
48 |
- |
6,60 |
54 |
- |
8,50 |
61 |
14 |
4 x 560 |
- |
4,40 |
41 |
- |
6,20 |
49 |
- |
7,30 |
54 |
- |
9,40 |
61 |
15 |
2 x 3 x 500 |
- |
4,65 |
41 |
- |
6,90 |
49 |
- |
7,80 |
51 |
- |
10,50 |
60 |
16 |
2 x 3 x 500 |
- |
5,00 |
41 |
- |
7,40 |
49 |
- |
8,40 |
51 |
- |
11,30 |
60 |
17 |
2 x 3 x 500 |
- |
5,50 |
41 |
- |
7,80 |
49 |
- |
9,00 |
51 |
- |
11,50 |
60 |
18 |
2 x 3 x 500 |
- |
6,40 |
42 |
- |
8,60 |
49 |
|
10,30 |
56 |
- |
13,30 |
63 |
The duties in the tables are according to ENV 327: air on +25°C and condensing temperature +40°C. Power input at +40°C and max. current at -30°C.
Sound power level dB(A) at 10 m distance according to ISO 3741.
We reserve the right to change the specification in this brochure without prior notice.
Fan and motor specifications
Model |
|
|
7 |
|
|
9 |
|
|
11 |
|
|
14 |
|
Fan |
Power |
|
|
|
|
|
|
|
|
|
|
|
|
D |
supply |
Airflow |
P.l. |
Current |
Airflow |
P.l. |
Current |
Airflow |
P.l. |
Current |
Airflow |
P.l. |
Current |
mm |
V |
l/min |
kW |
A |
l/min |
kW |
A |
l/min |
kW |
A |
l/min |
kW |
A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
350 |
230 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
1380 |
0,145 |
0,64 |
450 |
230 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
1325 |
0,480 |
2,30 |
350 |
400 |
- |
- |
- |
- |
- |
- |
1080 |
0,12 |
0,20 |
1380 |
0,145 |
0,38 |
450 |
400 |
710 |
0,11 |
0,30 |
920 |
0,17 |
0,52 |
1040 |
0,34 |
0,60 |
1340 |
0,450 |
0,90 |
500 |
400 |
620 |
0,14 |
0,32 |
880 |
0,24 |
0,60 |
1035 |
0,46 |
0,80 |
1330 |
0,650 |
1,15 |
560 |
400 |
620 |
0,20 |
0,48 |
860 |
0,39 |
0,92 |
1030 |
0,61 |
1,05 |
1330 |
0,800 |
1,55
|
- Safety switches installed next to fans
- Safety switches and cables suitable for frequency-converter operation
- Epoxy-surfaced aluminium panel
- Copper panel
- Painted case structure
- Water jets for compensating load peaks
- Fan-motor switchgear and control automation
- Special fans
- Special feet
- Rpm-controllers (continuous/stepped), see product Ecotronic