CGIW 10?45 kW

Model CGIW n-n, details of type and technical values available from the selection program

 

5-1

6-1

8-1

10-1

12-1

Cooling output kW 16 20 28 37 43
           
Power type V-Ph-Hz

400-3-50

400-3-50

400-3-50

400-3-50

400-3-50

Connected load kW 5,5 8,0 10,0 13,0 13,0
Operating current A 11,0 16,0 20,0 26,0 26,0
Pre-cutout A (slow) 20 25 32 40 40
           
Circuits 1 1 1 1 1
           
Refrigerant kg R410A 3,3 3,6 3,6 4,0 4,5
           
Dimensions          
Length mm 1240 1240 1240 1240 1240
Width mm 750 750 750 750 750
Height mm 1850 1850 1850 1850 1850
Freightage weight kg 290 300 310 320 340
Operating weight kg 270 280 290 300 320

Cooling output is given with the following values

  • Evaporator 7/12 °C, condenser 36/42 °C 
  • Ethylene glycol content 35 % 
  • in CGIA units, the cooling output is given at a condensation temperature of 45°C 
  • Connected load: compressors (additional equipment pumps,
    liquid chiller or condenser - fans stated separately) 
  • Operating current: suction pressure 5 bar, condensation pressure21 bar 
  • Sizes 32?100: pipe connections add +100 mm +-10 mm to the unit´s length 

Extrapolation from the output table is not permitted. Final technical selections to be made from our dimensioning software.
Chiller Oy reserves the right to make changes without separate notice.

Chiller accesories

Brochure CHSAM100112ENA.pdf

Dimensional drawing