Model CGIW n-n, details of type and technical values available from the selection program
5-1 |
6-1 |
8-1 |
10-1 |
12-1 |
|
Cooling output kW | 16 | 20 | 28 | 37 | 43 |
Power type V-Ph-Hz |
400-3-50 |
400-3-50 |
400-3-50 |
400-3-50 |
400-3-50 |
Connected load kW | 5,5 | 8,0 | 10,0 | 13,0 | 13,0 |
Operating current A | 11,0 | 16,0 | 20,0 | 26,0 | 26,0 |
Pre-cutout A (slow) | 20 | 25 | 32 | 40 | 40 |
Circuits | 1 | 1 | 1 | 1 | 1 |
Refrigerant kg R410A | 3,3 | 3,6 | 3,6 | 4,0 | 4,5 |
Dimensions | |||||
Length mm | 1240 | 1240 | 1240 | 1240 | 1240 |
Width mm | 750 | 750 | 750 | 750 | 750 |
Height mm | 1850 | 1850 | 1850 | 1850 | 1850 |
Freightage weight kg | 290 | 300 | 310 | 320 | 340 |
Operating weight kg | 270 | 280 | 290 | 300 | 320 |
Cooling output is given with the following values
- Evaporator 7/12 °C, condenser 36/42 °C
- Ethylene glycol content 35 %
- in CGIA units, the cooling output is given at a condensation temperature of 45°C
- Connected load: compressors (additional equipment pumps,
liquid chiller or condenser - fans stated separately) - Operating current: suction pressure 5 bar, condensation pressure21 bar
- Sizes 32?100: pipe connections add +100 mm +-10 mm to the unit´s length
Extrapolation from the output table is not permitted. Final technical selections to be made from our dimensioning software.
Chiller Oy reserves the right to make changes without separate notice.
Chiller accesories