CGIW 100?400 kW

Technical data

Model CGIW n-n, details of type and technical values available from the selection program

 

32-4

36-4

42-4

44-4

48-4

 

Cooling output kW 113 131 142

148

171

 

             
Power type V-Ph-Hz

400-3-50

400-3-50

400-3-50

400-3-50

400-3-50

 

Connected load kW 40,0 46,0 50,0 52,0 60,0

 

Operating current A 80,0 92,0 90,0 104,0 120,0

 

Pre-cutout A (slow) 100 125 160 160 160

 

             
Circuits 2 2 2 2 2

 

             
Refrigerant kg R410A 12,6 15,2 18,0 18,0 18,0

 

             
Dimensions            
Length mm 2100 2100 2100 2100 2100

 

Width mm 900 900 900 900 900

 

Height mm 1950 1950 1950 1950 1950

 

Freightage weight kg 985 1005 1085 1085 1125

 

Operating weight kg 960 980 1060 1060 1080

 

             
             

Model CGIW n-n, details of type and technical values available from the selection program

   
             

 

56-4

64-4

72-4

80-4

90-4

100-4

Cooling output kW 196 232 250 285 315 350
             
Power type V-Ph-Hz

400-3-50

400-3-50

400-3-50

400-3-50

400-3-50

400-3-50

Connected load kW

69,0 78,0 89,0 100,0

110,0

120,0

Operating current A 138,0 156,0 174,0 192,0

212,0

232,0

Pre-cutout A (slow) 200 200 200 250

315

315

             
Circuits 2 2 2 2 2 2
             
Refrigerant kg R410A 24,0 30,0 33,0 34,0

34,0

36,0

             
Dimensions            
Length mm 2100 2100 2100 2100 2100 2100
Width mm 900 900 900 900 900 900
Height mm 1950 1950 1950 1950 1950 1950
Freightage weight kg 1350 1400 1450 1600

1700

1800

Operating weight kg 1330 1380 1430 1700

1680

1780

Cooling output is given with the following values

  • Evaporator 7/12 °C, condenser 36/42°C
  • Ethylene glycol content 35 %
  • CGIAIn CGIA units, the cooling output is given at the condensation temperature 45°C
  • Connected load: compressors (additional equipment pumps,
    liquid chiller or condenser - fans stated separately)
  • Operating current: suction pressure 5 bar, condensation pressure 21 bar
  • Sizes 32?100: pipe connections add +100 mm +-10 mm to the unit´s length
     
    Extrapolation from the output table is not permitted. Final technical selections to be made from our dimensioning software.
    Chiller Oy reserves the right to make changes without separate notice.

Chiller accesories

Brochure CHSAM100112ENA.pdf

Dimensional drawing

Dimensional drawing