Technical data (with water coil)
CWDC=blowing downward
|
|
|
| |
|
|
|
| Nominal chilling output at room temperature 24? C, 50 %, water 7/12? C |
| |
|
|
|
| Device type |
75 |
90 |
110 |
| Total output kW |
26 |
35 |
43 |
| Sensible output kW |
26 |
32 |
36 |
| |
|
|
|
| Water-side pressure drops cooling |
|
|
| Radiator pressure drop kPa |
31,7 |
25,0 |
22,1 |
| 3-way valve size |
NS25 |
NS32 |
NS32 |
| 3-way valve pressure drop kPa |
19 |
15 |
25 |
| |
|
|
|
| Centrifugal fan 230V-1Ph-50Hz direct drive |
| Number |
2 |
2 |
2 |
| Air quantit m3/s |
2,3 |
2,3 |
2,3 |
| External pressure Pa |
60 |
60 |
60 |
| Motor output kW |
1,5 |
1,5 |
1,5 |
| |
|
|
|
| Centrifugal fans 400V-3Ph-50Hz v-belt drive |
| Number |
2 |
2 |
2 |
| Air quantity m3/s |
2,3 |
2,3 |
2,3 |
| External pressure Pa |
30 |
30 |
30 |
| Motor output kW |
2,2 |
2,2 |
2,2 |
| |
|
|
|
| Filters EU5 |
|
|
|
| Number |
1 |
1 |
1 |
| Size: downward blowing |
560x650 |
560x650 |
560x650 |
| |
|
|
|
| After-heating 400V-3Ph-50Hz |
|
|
| Heating output kW |
6,6 |
6,6 |
6,6 |
| Number of elements |
2 |
2 |
4 |
| Number of steps |
2 |
2 |
3 |
| |
|
|
|
| Humidification 400V-3Ph-50Hz |
|
|
|
| Humidification output kg |
4,7 |
4,7 |
9,4 |
| Connected load kW |
3,4 |
3,4 |
6,9 |
| |
|
|
|
| Dimensions and weight |
|
|
|
| Width mm |
1775 |
1775 |
1775 |
| Depth mm |
650 |
650 |
650 |
| Height mm |
1920 |
1920 |
1920 |
| Weight kg |
370 |
370 |
370 |
| |
|
|
|
| Connections |
|
|
|
| Cold water " |
1 |
1 1/4 |
1 1/4 |
| Humidifier mm |
6 |
6 |
6 |
| Drain mm |
32 |
32 |
32 |
| |
|
|
|
| Unit´s electrical connected load with v-belt drive 400V-3Ph-50Hz |
| Types A and E kW |
2,2 |
2,2 |
2,2 |
| Type B kW |
8,8 |
8,8 |
14,2 |
| Type C kW |
5,6 |
5,6 |
9,1 |
| Type D kW |
12,2 |
12,2 |
21,1 |
| |
|
|
|
| A=cooling |
|
|
|
| B=cooling + electrical heating |
|
|
| C=cooling + humidification |
|
|
|
| D=cooling + heating + humidification + drying |
|
| E = water heating instead of electrical heating |
|
| When direct-drive version, the fan power-draw difference must be deducted from the connected load |
CWUC=blowing upward
|
|
|
| |
|
|
|
| Nominal cooling output at room temperature 24? C, 50 %, water 7/12? C |
| |
|
|
|
| Device type |
75 |
90 |
110 |
| Total output kW |
26 |
35 |
43 |
| Sensible output kW |
26 |
32 |
36 |
| |
|
|
|
| Water-side pressure drops cooling |
|
|
| Coil pressure drop kPa |
31,7 |
25,0 |
22,1 |
| 3-way valve size |
NS25 |
NS32 |
NS32 |
| 3-way valve pressure drop kPa |
19 |
15 |
25 |
| |
|
|
|
| Centrifugal fans 230V-1Ph-50Hz direct drive |
| Number |
2 |
2 |
2 |
| Air quantity m3/s |
2,3 |
2,3 |
2,3 |
| External pressure Pa |
30 |
30 |
30 |
| Motor output kW |
1,5 |
1,5 |
1,5 |
| |
|
|
|
| Centrifugal fans 400V-3Ph-50Hz v-belt drive |
| Number |
2 |
2 |
2 |
| Air quantity m3/s |
2,3 |
2,3 |
2,3 |
| External pressure Pa |
30 |
30 |
30 |
| Motor output kW |
2,2 |
2,2 |
2,2 |
| |
|
|
|
| Filters EU5 |
|
|
|
| Number |
2 |
2 |
2 |
| Size: downward blowing |
600x600 |
600x600 |
600x600 |
| |
|
|
|
| After-heating 400V-3Ph-50Hz |
|
|
| Heating output kW |
6,6 |
6,6 |
12,0 |
| Number of elements |
2 |
2 |
4 |
| Number of steps |
2 |
2 |
3 |
| |
|
|
|
| Humidification 400V-3Ph-50Hz |
|
|
|
| Humidification output kg |
4,7 |
4,7 |
9,4 |
| Connected load kW |
3,4 |
3,4 |
6,9 |
| |
|
|
|
| Dimensions and weight |
|
|
|
| Width mm |
1775 |
1775 |
1775 |
| Depth mm |
650 |
650 |
650 |
| Height mm |
1920 |
1920 |
1920 |
| Weight kg |
370 |
370 |
370 |
| Exhaust chamber height 500 mm |
|
| (to be added to height of unit, model CWUC) |
|
| |
|
|
|
| Connections |
|
|
|
| Cold water " |
1 |
1 1/4 |
1 1/4 |
| Humidifier mm |
6 |
6 |
6 |
| Drain mm |
32 |
32 |
32 |
| |
|
|
|
| Unit´s electrical connected load with v-belt drive 400V-3Ph-50Hz |
| Types A and E kW |
2,2 |
2,2 |
2,2 |
| Type B kW |
8,8 |
8,8 |
14,2 |
| Type C kW |
5,6 |
5,6 |
9,1 |
| Type D kW |
12,2 |
12,2 |
21,1 |
| |
|
|
|
| A=cooling |
|
|
|
| B=cooling + electrical heating |
|
|
| C=cooling + humidification |
|
|
|
| D=cooling + heating + humidification + drying |
|
| E = water heating instead of electrical heating |
|
| When direct-drive version, the fan power-draw difference must be deducted from the connected load |