CGIW 10?45 kW

Model CGIW n-n-V-P1-P2-(P3), details of type and technical values available from the selection program

           
 

5-1

6-1

8-1

10-1

12-1

Cooling output kW 16 20 28 37 43
           
Power type V-Ph-Hz

400-3-50

400-3-50

400-3-50

400-3-50

400-3-50

Connected load kW 7,3 9,8 11,8 14,8 14,9
Operating current A 14,2 19,2 23,2 30,0 30,0
Pre-cutout A (slow) 20 25 32 40 40
           
Circuits 1 1 1 1 1
           
Refrigerant kg R410A 3,3 3,6 3,6 4,0 4,5
Header tank l 300 300 300 300 300
           
Dimensions          
Length mm 1240 1240 1240 1240 1240
Width mm 750 750 750 750 750
Height mm 1850 1850 1850 1850 1850
Freightage weight kg 240 250 255 275 290
Operating weight kg 470 480 490 500 520

Cooling output is given with the following values

  • Evaporator 7/12 °C, condenser 36/42 °C
  • Ethylene glycol content 35 %
  • in CGIA units, the cooling output is given at a condensation temperature of 45 °C
  • Connected load: compressors (additional equipment pumps,
    liquid chiller or condenser - fans stated separately)
  • Operating current: suction pressure 5 bar, condensation pressure 21 bar 

(P3) only in model CGIW. Extrapolation from the output table is not permitted.
Final technical selections to be made from our dimensioning software.
Chiller Oy reserves the right to make changes without separate notice.