Model CHT-5...12-1S-X-P1-P3-STD, type and selections are available from Chiller Oy´s sales engineers or from an authorized sales organization.
| Model CHT | 5-1 | 6-1 | 8-1 | 10-1 | 12-1 |
| Heating cap. kW | 14,8 | 19,4 | 25,8 | 34,4 | 38,5 |
| Cap. adjusting | 0;100% | 0;100% | 0;100% | 0;100% | 0;100% |
| Mains | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 |
| Power input kW | 7,6 | 10,1 | 13,6 | 17,1 | 19,6 |
| Running amps A | 17,6 | 20,6 | 24,1 | 30,1 | 34,6 |
| Precut-out fuse A (slow) | 20 | 25 | 32 | 40 | 40 |
| Nominal flows: | |||||
| Cold side kg/s | 0,77 | 1,00 | 1,31 | 1,79 | 1,97 |
| Hot side kg/s | 0,68 | 0,89 | 1,18 | 1,57 | 1,76 |
| Refr. R410A kg | 3,3 | 3,6 | 3,6 | 4 | 4,5 |
| Dimensions: | |||||
| Length mm | 1240 | 1240 | 1240 | 1240 | 1240 |
| Width mm | 750 | 750 | 750 | 750 | 750 |
| Height mm | 1850 | 1850 | 1850 | 1850 | 1850 |
Capacity by values 0/-3°C (30% etanol) and 44/50°C (water)
Power input: compressor and pumps P1 and P3
Exact selection data from sales engineer (on base of concrete project requirements)